SOL-I-IS-5E
Mecer InfiniSolar E 5.5KW Single Phase 6500W MPPT - bi directional with grid
Mecer InfiniSolar E 5.5KW Single Phase 6500W MPPT - bi directional with grid, NO parallel ability, 48V DC, Pure sinewave, 40A Maximum AC Input Current, 60 A Maximum Solar Charge Current, 2x MPP Trackers, 6500W Maximum PV Input Power, 5500W Rated Output Power
Specifications:
© 2019 Respective owners and brand holders. This table has been carefully researched and generated by Laptop Direct CC (https://www.laptopdirect.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. | |
Specifications![]() | |
Product Code | SOL-I-IS-5E![]() |
MODEL | InfiniSolar E 5.5KW |
Maximum PV Input Power | 6500W |
Rated Output Power | 5500W |
Maximum Charging Power | 2880 W |
GRID-TIE OPERATION | |
PV INPUT (DC) | |
Nominal DC Voltage / Maximum DC Voltage | 360 VDC / 500 VDC |
Start-up Voltage / Initial Feeding Voltage | 116 VDC / 150 VDC |
MPP Voltage Range | 120 VDC ~ 450 VDC |
Number of MPP Trackers / Maximum Input Current | 2 / 2 x 13 A |
GRID OUTPUT (AC) | |
Nominal Output Voltage | 202/208/220/230/240 VAC |
Output Voltage Range | 184 - 264.5 VAC |
Max. Output Current | 23.9A |
Power Factor | > 0.99 |
EFFICIENCY | |
Maximum Conversion Efficiency (DC/AC) | 0.96 |
European Efficiency@ Vnominal | 0.95 |
OFF-GRID OPERATION | |
AC INPUT | |
AC Start-up Voltage / Auto Restart Voltage | 120 - 140 VAC / 180 VAC |
Acceptable Input Voltage Range | 170 -280 VAC |
Maximum AC Input Current | 40 A |
PV INPUT (DC) | |
Maximum DC Voltage | 500 VDC |
MPP Voltage Range | 120 VDC ~ 450 VDC |
Number of MPP Trackers / Maximum Input Current | 2 / 2 x 13 A |
BATTERY MODE OUTPUT (AC) | |
Nominal Output Voltage | 202/208/220/230/240 VAC |
Output Waveform | Pure sinewave |
Efficiency (DC to AC) | 0.93 |
HYBRID OPERATION | |
PV INPUT (DC) | |
Nominal DC Voltage / Maximum DC Voltage | 360 VDC / 500 VDC |
Start-up Voltage / Initial Feeding Voltage | 116 VDC / 150 VDC |
MPP Voltage Range | 120 VDC ~ 450 VDC |
Number of MPP Trackers / Maximum Input Current | 2 / 2 x 13 A |
GRID INPUT | |
Nominal Output Voltage | 202/208/220/230/240 VAC |
Output Voltage Range | 184 - 264.5 VAC |
Max. Output Current | 23.9A |
AC INPUT | |
AC Start-up Voltage / Auto Restart Voltage | 120 - 140 VAC / 180 VAC |
Acceptable Input Voltage Range | 170 -280 VAC |
Maximum AC Input Current | 40A |
BATTERY MODE OUTPUT (AC) | |
Nominal Output Voltage | 202/208/220/230/240 VAC |
Efficiency (DC to AC) | 0.93 |
BATTERY & CHARGER | |
Nominal DC Voltage | 48 VDC |
Maximum Solar Charge Current | 60 A |
GENERAL | |
PHYSICAL | |
Dimension, D x W x H (mm) | 110 x 450 x 445 |
Net Weight (kgs) | 16 |
INTERFACE | |
External Safety Box (Optional) | RS-232/USB |
Communication ports | Optional SNMP, Modbus and AS-400 cards |
ENVIRONMENT | |
Humidity | 0 ~ 90% RH (Non-condensing) |
Operating Temperature | 0 to 40ºC |
Altitude | 0 ~ 1000 m |